Specifications
Overview
The J, MJ and VHV Series products are Power Distribution Units (PDU) intended for connection to
a 15 or 20 Amp AC Mains circuit
. The PDUs are designed to be powered by either a single phase
or a three phase AC input circuit. Three phase units can be configured for either a delta or wye
input connection. J, MJ and VHV Series PDUs can optionally be configured with a Geist Current
Meter that provides local monitoring and display of each output circuit current. Alternatively, J,
MJ and VHV Series PDUs can be configured with a Geist Current Monitoring Meter that provides
both local and remote monitoring of input and output line current. J and VNV Series PDUs can
also be configured with advanced wireless technology from Packet Power which allows for remote
monitoring of input and output power through a wirelessly connected gateway.
Environmental
Temperature
Operating (J, VHV): 10°C (50°F) min 45°C (113°F) max
Operating (MJ): 10°C (50°F) min 25°C (113°F) max
Storage: -25°C (-13°F) min 65°C (149°F) max
Humidity
Operating: 5% min 95% max (non-condensing)
Storage: 5% min 95% max (non-condensing)
Elevation
Operating: 0 m (0 ft) min 2000 m (6561 ft) max
Storage: 0 m (0 ft) min 15240 m (50000 ft) max
Electrical
See nameplate for unit ratings.
Receptacle Ratings
NEMA 5-15R or L5-15R 125 Volts, 15 Amp
NEMA 5-20R or L5-20R 125 Volts, 20 Amp
NEMA 6-20R or L6-20R 250 Volts, 20 Amp
IEC-320 C13 125/250 Volt, 15 Amp (per Receptacle Bank)
IEC-320 C19 125/250 Volt, 20 Amp
Networking (For Current Monitoring Meter Units Only)
Protocols
HTTP, ICMP, DHCP, TCP/IP, FTP
Global Versions of the VHV Series are intended to be connected to a 16 Amp AC Mains Branch
Circuits